Violation Detail
Standard Cited: 19100303 B07 I General.
Inspection Nr: 1519476.015
Citation: 01011B
Citation Type: Serious
Abatement Status: Not Completed - Solicitor Advised
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/10/2021
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 02/13/2023
Gravity: 5
Report ID: 0418100
Contest Date: 10/05/2021
Final Order: 01/30/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/30/2023 | $0.00 | 02/13/2023 | Serious | |
Penalty | C: Contested | 12/13/2021 | $0.00 | 10/28/2021 | Serious | |
Penalty | Z: Issued | 09/10/2021 | $0.00 | 10/28/2021 | Serious |
Text For Citation: 01 Item/Group: 011B Hazard:
29 CFR 1910.303(b)(7)(i): Unused openings in boxes, raceways, auxiliary gutters, cabinets, equipment cases, or housings were not effectively closed to afford protection substantially equivalent to the wall of the equipment. a - On or about June 10, 2021, at Plant 4, in the outside MCC electrical room, at the LTS2 and LTS4 breakers on the 480v panel, employees resetting breakers were exposed to electrical shock as the employer did not ensure unused openings in the cabinet were effectively closed. b - On or about June 10, 2021, at Plant 4, in the outside MCC electrical room, at the unidentified electrical panel (110/220v), employees resetting breakers were exposed to electrical shock as the employer did not ensure unused openings in the cabinet were effectively closed.