Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1037332.015
Citation: 01011B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/30/2015
Nr Instances: 4
Nr Exposed: 60
Abatement Date: 07/31/2015
Gravity:
Report ID: 0625400
Contest Date:
Final Order: 08/20/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/20/2015 | $0.00 | 07/31/2015 | Other | |
Penalty | Z: Issued | 07/30/2015 | $0.00 | 07/31/2015 | Serious |
Text For Citation: 01 Item/Group: 011B Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about February 9, 2015 and in times prior thereto, the following equipment was not provided with proper strain relief, exposing employees to the hazards of electrical shock: a. A 480 VAC cord coming from the load side of disconnect 4, located in the shipping and receiving area. b. A 460 VAC cord entering the cabinet of Compare L75 RS air compressor, located in the outside utility area. c. A 480 VAC cord to unit 167 disconnect, located in the production area. d. A 480 VAC cord on the load side of Chiller I 14 disconnect, located in the pail area.