Violation Detail
Standard Cited: 19100119 F04 Process safety management of highly hazardous chemicals.
Inspection Nr: 810501.015
Citation: 01011A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $5,950.00
Issuance Date: 07/01/2013
Nr Instances: 1
Nr Exposed: 10
Abatement Date: 11/01/2013
Gravity: 10
Report ID: 0627510
Contest Date:
Final Order: 07/24/2013
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/24/2013 | $5,950.00 | 11/01/2013 | Serious | |
Penalty | Z: Issued | 07/01/2013 | $7,000.00 | 07/26/2013 | Serious |
Text For Citation: 01 Item/Group: 011A Hazard:
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; and confined space entry. The employer did not ensure that safe work practices, which include specific lockout/tagout procedures, were established and implemented for all equipment such as, but not limited to, a) low stage compressor (Comp B-2) in the mechanical room. b) high stage compressor (Comp H-1) in the mechanical room. c) high stage compressor (Comp H-2) in the mechanical room. d) swing compressor (Comp S-1) in the mechanical room. e) evaporative condensers (EC-1&2) throughout the facility. f) fab floor cooler (FF-1 through FLD-2) in the fabrication floor.