Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1571874.015
Citation: 01011A
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $4,445.00
Current Penalty: $3,333.75
Issuance Date: 02/18/2022
Nr Instances: 1
Nr Exposed: 4
Abatement Date:
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 03/25/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/25/2022 | $3,333.75 | Serious | ||
Penalty | Z: Issued | 02/18/2022 | $4,445.00 | Serious |
Text For Citation: 01 Item/Group: 011A Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Receiving Area: On, or about, January 21, 2022, a metal railing had been installed in front of the main service entrance switchboards, including an enclosure for the solar generation system and an enclosure for the buss system, which did not allow the minimum working space to be maintained in front of the equipment.