Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1417910.015
Citation: 01011A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,304.00
Current Penalty: $2,652.00
Issuance Date: 12/20/2019
Nr Instances: 1
Nr Exposed: 12
Abatement Date: 01/13/2020
Gravity: 10
Report ID: 0521400
Contest Date:
Final Order: 01/07/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 01/07/2020 | $2,652.00 | 01/13/2020 | Serious | |
Penalty | Z: Issued | 12/20/2019 | $5,304.00 | 01/13/2020 | Serious |
Text For Citation: 01 Item/Group: 011A Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by this standard, live parts of electric equipment operating at 50 volts or more shall be guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the following means: On or about 24 July 2019, the electrical circuit panel enclosures were left open and exposed employees to fire and electrical shock hazards while accessing the panels to switch the shop lights ON and OFF, to reset the fuses when they pop, and where inadvertent contact with energized parts operating between 110 to 480 Volts AC was likely. Abatement documentation is required for this item in accordance with 29 CFR 1903.19(d).