Violation Detail
Standard Cited: 19100304 G01 IV A Wiring design and protection.
Inspection Nr: 1237124.015
Citation: 01011A
Citation Type: Serious
Abatement Date: 11/13/2017 2
Initial Penalty: $2,897.00
Current Penalty: $2,000.00
Issuance Date: 10/19/2017
Nr Instances: 1
Nr Exposed: 11
Related Event Code (REC):
Gravity: 5
Report ID: 0627700
Contest Date:
Final Order: 12/21/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/21/2017 | $2,000.00 | 11/13/2017 | Serious | |
Penalty | Z: Issued | 10/19/2017 | $2,897.00 | 11/13/2017 | Serious |
Text For Citation: 01 Item/Group: 011A Hazard:
29 CFR 1910.304(g)(1)(iv)(A): AC systems of 50 volts to 1000 volts were not grounded under the following condition: the system was so grounded that the maximum voltage to ground on the ungrounded conductor does not exceed 150 Volts, unless exempted by paragraph (g)(1)(v) of this section: Drilling rig: On or about May 29, 2017, employees operated a drilling rig during the drilling of an oil/gas well used a skid mounted generator to provide electricity to the rig and the generator was not grounded, exposing the employees to the hazard of electrical shock.