Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1100097.015
Citation: 01011A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,600.00
Current Penalty: $3,700.00
Issuance Date: 04/11/2016
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 05/05/2016
Gravity: 5
Report ID: 0728900
Contest Date:
Final Order: 04/28/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 04/28/2016 | $3,700.00 | 05/05/2016 | Serious | |
| Penalty | Z: Issued | 04/11/2016 | $6,600.00 | 05/05/2016 | Serious |
Text For Citation: 01 Item/Group: 011A Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: The employer is failing to protect employees from a fire and electrical hazards. This was most recently documented at 1329 West Highway 6, Holdrege Nebraska when an ACE 5 outlet surge suppressor that was rated at 15 Amps was being used to provide power for four 10 Amp Kenex Automatic Leak Tester machines, Serial # GLTM271113 in the Leak Test area of the Front Molding Area. Each of these leak testers where rated at a maximum amperage of 10 Amps for a total potential load on the 15 Amp surge suppressor of 40 Amps.
Translate