Violation Detail
Standard Cited: 19100269 L08 V Electric Power Generation, Transmission, and Distribution.
Inspection Nr: 1749405.015
Citation: 01011
Citation Type: Serious
Abatement Status:
Initial Penalty: $16,131.00
Current Penalty: $16,131.00
Issuance Date: 11/20/2024
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 12/03/2024
Gravity: 10
Report ID: 0213100
Contest Date: 12/19/2024
Final Order:
Related Event Code (REC): A
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 12/19/2024 | $16,131.00 | 12/03/2024 | Serious | |
Penalty | Z: Issued | 11/20/2024 | $16,131.00 | 12/03/2024 | Serious |
Text For Citation: 01 Item/Group: 011 Hazard:
29 CFR 1910.269(l)(8)(v): The employer did not ensure that each employee exposed to hazards from electric arcs wore protective clothing and other protective equipment that had an arc rating greater than or equal to the heat energy estimated under paragraph (l)(8)(ii) of this section whenever that estimate exceeded 2.0 Cal/cm2: (a) Mount Ida Hydro Station, Control room level: On or about May 21, 2024, employees were conducting maintenance on an Allis Chalmers MA-250C circuit breaker in a 4160-volt switchgear housing. The employer failed to provide the employees with FR clothing, rubber insulating glove, heavy-duty work shoes, and head protection.