Violation Detail
Standard Cited: 19100119 J05 Process safety management of highly hazardous chemicals.
Inspection Nr: 1722534.015
Citation: 01011
Citation Type: Serious
Abatement Status:
Initial Penalty: $10,372.00
Current Penalty: $10,372.00
Issuance Date: 07/22/2024
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 09/06/2024
Gravity: 5
Report ID: 0317900
Contest Date: 08/19/2024
Final Order:
Related Event Code (REC): R
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | C: Contested | 10/28/2024 | $10,372.00 | 09/06/2024 | Serious | |
| Penalty | Z: Issued | 07/22/2024 | $10,372.00 | 09/06/2024 | Serious |
Text For Citation: 01 Item/Group: 011 Hazard:
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) before use: a) 1323 Conshohocken Rd. Plymouth Meeting, PA 19462 - Tank Farm: On or about June 28, 2024 the employer did not correct deficiencies noted in the 2/24/24 TAI report where multiple points in Tank A108's shell were measured below the documented t(min) thickness. Failure to correct deficiencies in equipment outside acceptable limits can result in catastrophic release of flammable materials.