Violation Detail
Standard Cited: 19100110 C06 II Storage and handling of liquefied petroleum gases.
Inspection Nr: 998870.015
Citation: 01010C
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/17/2015
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0627700
Contest Date:
Final Order: 04/14/2015
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/14/2015 | $0.00 | Serious | ||
Penalty | Z: Issued | 03/17/2015 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 010C Hazard:
29 CFR 1910.110(c)(6)(ii): Regulators and low-pressure relief devices were not rigidly attached to the cylinder valves, cylinders, supporting standards, the building walls or otherwise rigidly secured and were not so installed or protected that the elements (sleet, snow, or ice) will not affect their operation: a. On or about October 15, 2014, at the west side of the paint building, a regulator was not provided at the valve of a propane cylinder to which a hose and torch were attached which exposes employees to fire and explosion hazards.