Violation Detail
Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1393269.015
Citation: 01010C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,934.00
Current Penalty: $0.00
Issuance Date: 07/15/2019
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 03/01/2020
Gravity: 10
Report ID: 0522500
Contest Date: 08/05/2019
Final Order: 03/04/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | J: ALJ Decision | 03/04/2020 | $0.00 | 03/01/2020 | Serious | |
Penalty | C: Contested | 08/21/2019 | $11,934.00 | 08/19/2019 | Serious | |
Penalty | Z: Issued | 07/15/2019 | $11,934.00 | 08/19/2019 | Serious |
Text For Citation: 01 Item/Group: 010C Hazard:
29 CFR 1910.335(a)(1)(i): Employees working in areas where there are potential electrical hazards shall be provided with,and shall use, electrical protective equipment that is appropriate for the specific parts of the body to be protected and for the work to beperformed.Note: Personal protective equipment requirements are contained in subpart I of this part. a. At the workplace, for employees who routinely perform work on or near energized parts (460 VAC) such as testing, troubleshooting, voltage measuring, and other tasks in and around the cranes, employees did not wear and were not provided with the necessary personal protective equipment to protect employees from shock, arc flash, or arc blast.