Violation Detail
Standard Cited: 19100303 G01 III General.
Inspection Nr: 1566871.015
Citation: 01010B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/02/2022
Nr Instances: 1
Nr Exposed: 15
Abatement Date: 01/03/2023
Gravity: 1
Report ID: 0316700
Contest Date:
Final Order: 06/21/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/21/2022 | $0.00 | 01/03/2023 | Serious | |
Penalty | Z: Issued | 06/02/2022 | $0.00 | 06/21/2022 | Serious |
Text For Citation: 01 Item/Group: 010B Hazard:
29 CFR 1910.303(g)(1)(iii):The employer did not ensure that at least one entrance of sufficient area was provided to give access to the working space about electric equipment 600 Volts, nominal, or less. a. The maintenance shop - On or about February 2, 2022, the employer had parked a scissor lift under the rack system that had blocked access to the disconnect box for the forklift charging terminal, exposing employees to an electrical hazard. b. The White Glue Totes - On or about February 2, 2022, the employer had tube storage units parked in front and on the back side was obstructed by the glue tote system which together blocked access to the disconnect box for the white glue totes, exposing employees to an electrical hazard. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.