Violation Detail
Standard Cited: 19100305 G01 IV D Wiring methods, components, and equipment for general use.
Inspection Nr: 1069465.015
Citation: 01010B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/04/2015
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 12/16/2015
Gravity: 1
Report ID: 0112600
Contest Date:
Final Order: 12/18/2015
Related Event Code (REC): C
Emphasis:
Substance: 8870
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/18/2015 | $0.00 | 12/16/2015 | Serious | |
Penalty | Z: Issued | 12/04/2015 | $0.00 | 12/16/2015 | Serious |
Text For Citation: 01 Item/Group: 010B Hazard:
29 CFR 1910.305(g)(1)(iv)(D): Flexible cords and cables were used where attached to building surfaces: Furnace 9505 in Forge Shop, Wyman and Gordon, 244 Worcester Street, North Grafton, Massachusetts; The flexible cords being used to power equipment were attached to the building with wire ties. a. The air compressor on the lower level of the 9505 furnace was permanently attached to the metal decking using wire ties. b. Flexible cord was attached to the conduit powering a fire control cabinet in the 50,000 ton press pump room