Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 936564.015
Citation: 01010A
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $1,600.00
Current Penalty: $960.00
Issuance Date: 12/23/2013
Nr Instances: 1
Nr Exposed: 2
Abatement Date:
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 01/09/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 01/09/2014 | $960.00 | Serious | ||
| Penalty | Z: Issued | 12/23/2013 | $1,600.00 | Serious |
Text For Citation: 01 Item/Group: 010A Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts was less than indicated in Table S-1 of Subpart S of Part 1910: Processing Area, Exterior Wall Behind Opti-Line: On, or about, August 29, 2013, a concrete block had been placed in front of the Square D I-Line distribution panel for protection, but did not allow clear working space in front of the panel.