Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
This violation item has been deleted.
Inspection Nr: 966624.015
Citation: 01010
Citation Type: Serious
Abatement Date: 10/31/2014 2
Initial Penalty: $2,100.00
Current Penalty: $0.00
Issuance Date: 10/03/2014
Nr Instances: 1
Nr Exposed: 3
Related Event Code (REC):
Gravity: 1
Report ID: 0317900
Contest Date:
Final Order: 10/08/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/08/2014 | $0.00 | 10/31/2014 | Serious | |
Penalty | Z: Issued | 10/03/2014 | $2,100.00 | 10/13/2014 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard:
29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." a) Production area - On or about April 8, 2014, Circuit breakers used to switch the overhead 277V fluorescent lights on/off were not of type SWD.