Violation Detail
Standard Cited: 19100305 B02 Wiring methods, components, and equipment for general use.
Inspection Nr: 964439.015
Citation: 01010
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $1,600.00
Current Penalty: $1,225.00
Issuance Date: 09/24/2014
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 10/30/2014
Gravity: 5
Report ID: 0213100
Contest Date:
Final Order: 10/08/2014
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/08/2014 | $1,225.00 | 10/30/2014 | Serious | |
| Penalty | Z: Issued | 09/24/2014 | $1,600.00 | 10/10/2014 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard:
29 CFR 1910.305(b)(2): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: (a) Compressor room: On or prior to 3/27/14, Square D motor controllers and Paragon time controllers (below defrost timer switches) located along the north wall of the room were missing components and/or not completely covered and enclosed/kept closed. (b) Outside boxing room: On or about 3/27/14, Panel PB-PF-1, circuit breaker position 30 was missing a blank or cover, exposing the bus bar. (c) Electrical room: On or about 3/27/14, Panel UP-1, circuit breakers position 19, 21, and below CB 29 were missing a blank or cover, exposing the bus bar.