Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 313017774
Citation: 01010
Citation Type: Serious
Abatement Date: 08/05/2011
Initial Penalty: $7,000.00
Current Penalty:
Issuance Date: 06/21/2011
Nr Instances: 2
Nr Exposed: 5
Related Event Code (REC):
Gravity: 10
Report ID: 0524530
Contest Date: 07/13/2011
Final Order: 09/10/2012
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 09/10/2012 | 08/05/2011 | Serious | ||
Penalty | Z: Issued | 06/21/2011 | $7,000.00 | 08/05/2011 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard: CHEMNEP
29 CFR 1910.119(j)(4)(i): Inspections and tests were not performed on process equipment: (a)The deadleg on line 2"-PFF-413 was identified with a thickness measurement location but was not inspected on piping inspection report MTW-A2350-07, 9/28/09. (b)The deadlegs/inspection ports on line 6"-PFF-401 were identified with thickness measurement locations but were not inspected on piping inspection reports TKF-RPT- PP180-014, 6/4/08 and MTW-A2350-14, 9/28/09. (c)The HF Hose Adapter Unloading Assembly connection comprised of 1" schedule 80 pipe threads, union, and bushing leaked on 3/10/11. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).