Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1744069.015
Citation: 01010
Citation Type: Other
Abatement Status: Corrected During Inspection
Initial Penalty: $16,131.00
Current Penalty: $8,065.00
Issuance Date: 10/18/2024
Nr Instances: 1
Nr Exposed: 15
Abatement Date:
Gravity: 10
Report ID: 0522500
Contest Date: 11/11/2024
Final Order: 10/20/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 10/20/2025 | $8,065.00 | Other | ||
| Penalty | C: Contested | 11/12/2024 | $16,131.00 | Serious | ||
| Penalty | Z: Issued | 10/18/2024 | $16,131.00 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard:
29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. Requirements for each of these options are as follows: a. On or about April 23, 2024, and at times prior, located in the CR1 Reactor Room, there was an electrical installation labeled as intrinsically safe, that was not properly installed for the Class 1, Division 1, classified location, in that there was a screw missing that resulted in a gap and improper sealing of the electrical equipment. As a result, employees working on and in the vicinity of the CR1 PSM-covered process were exposed to fire and explosion hazards.