Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1259236.015
Citation: 01010
Citation Type: Serious
Abatement Date: 12/27/2017 2
Initial Penalty: $2,897.00
Current Penalty: $1,000.00
Issuance Date: 11/30/2017
Nr Instances: 1
Nr Exposed: 7
Related Event Code (REC):
Gravity: 5
Report ID: 0522300
Contest Date:
Final Order: 12/21/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/21/2017 | $1,000.00 | 12/27/2017 | Serious | |
Penalty | Z: Issued | 11/30/2017 | $2,897.00 | 12/27/2017 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard:
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures, or by any of the following means identified in sub-paragraphs (A)through (D) of this paragraph: On or about August 09, 2017, the employer failed to ensure that a 240 volts, 3phase service panel located on the north wall, was effectively closed and/or free from damage. The service panel had several unused circuit breaker opening, exposing the energized bus bar.