Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1165746.015
Citation: 01010
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $12,675.00
Current Penalty: $12,675.00
Issuance Date: 01/20/2017
Nr Instances: 2
Nr Exposed: 40
Related Event Code (REC):
Gravity: 10
Report ID: 0418100
Contest Date:
Final Order: 02/17/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/17/2017 | $12,675.00 | Serious | ||
Penalty | Z: Issued | 01/20/2017 | $12,675.00 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): a. On or about 7/26/2016, employees were exposed to potential electrical shock, electrical burn, and electrocution hazards where exposed live electrical parts were not guarded against accidental contact at locations including but not limited to Line 20, printer 9, UV Lamp power wires were not installed properly. The 2-wire system was powered by a 3-wire flexible cord connected with wire nuts and the ground wire was not connected to the panel. b. On or about 7/26/2016, employees were exposed to potential electrical shock, electrical burn, and electrocution hazards where exposed live electrical parts were not guarded against accidental contact at locations including but not limited to at Line 25 Bagger quad outlet right side missing screw allowing for the receptacle to be pushed into the box when male plug is inserted, exposing the live 120V electrical parts inside.