Violation Detail
Standard Cited: 19100305 D02 Wiring methods, components, and equipment for general use.
Inspection Nr: 1133673.015
Citation: 01010
Citation Type: Other
Abatement Date: 05/18/2016 2
Initial Penalty: $3,850.00
Current Penalty: $1,000.00
Issuance Date: 05/06/2016
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC):
Gravity:
Report ID: 0418600
Contest Date:
Final Order: 05/24/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/24/2016 | $1,000.00 | 05/18/2016 | Other | |
Penalty | Z: Issued | 05/06/2016 | $3,850.00 | 05/18/2016 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard:
29 CFR 1910.305(d)(2): Panel boards were not mounted in cabinets, cutout boxes, or enclosures approved for the purpose and were not dead front: a) Grinder Electrical Room; On or about March 15, 2016 and at times prior thereto the employer exposed employees to electrical hazards in that employees were allowed to operate breakers mounted in a cabinet with the front cover removed and was not dead front exposing live unguarded 480 volts 3 phase AC electrical parts.