Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1090066.015
Citation: 01010
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,800.00
Current Penalty: $2,800.00
Issuance Date: 12/02/2015
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 12/08/2015
Gravity: 5
Report ID: 0524500
Contest Date:
Final Order: 12/29/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 12/02/2015 | $2,800.00 | 12/08/2015 | Serious |
Text For Citation: 01 Item/Group: 010 Hazard:
29 CFR 1910.305(b)(2)(i): Pull boxes, junction boxes, and fittings were not provided with covers approved for the purpose: An employee working in the Work Room of the Grandview Outlet was exposed to electrical shock hazards because the electrical outlet located on the east wall was not equipped with a suitable cover.