Violation Detail
Standard Cited: 19100335 A02 I A Safeguards for personnel protection.
Inspection Nr: 1446527.015
Citation: 01009C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,675.00
Current Penalty: $0.00
Issuance Date: 04/17/2020
Nr Instances: 2
Nr Exposed: 7
Abatement Date: 05/13/2020
Gravity: 5
Report ID: 0111700
Contest Date:
Final Order: 05/11/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/11/2020 | $0.00 | 05/13/2020 | Serious | |
Penalty | Z: Issued | 04/17/2020 | $8,675.00 | 05/13/2020 | Serious |
Text For Citation: 01 Item/Group: 009C Hazard:
29 CFR 1910.335(a)(2)(i)(A): Fuse handling equipment, insulated for the circuit voltage was not used to remove or install fuses when fuse terminals were energized. a. PM #9, Drive Room 2- On or about November 27, 2019, an employee opening the 2400 volt fused disconnect for the #2 Jones Refiner was not protected from an electric shock hazard where a wooden stick, that was not rated for 2400 volts, was used to open the fused disconnect. b. PM #9, Drive Room 1- An employee opening the 2400 volt fused disconnect for the Spare Press Vacuum Pump was not protected from an electric shock hazard where a wooden stick, that was not rated for 2400 volts, was used to open the fused disconnect.