Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1687789.015
Citation: 01009B
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/29/2024
Nr Instances: 2
Nr Exposed: 2
Abatement Date: 02/23/2024
Gravity: 10
Report ID: 0317300
Contest Date:
Final Order: 02/28/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | Z: Issued | 01/29/2024 | $0.00 | 02/23/2024 | Serious |
Text For Citation: 01 Item/Group: 009B Hazard:
29 CFR 1910.304(f)(1)(viii):29 CFR 1910.304(f)(1)(viii): Circuit breakers used as switches in 120-volt and 277-volt, fluorescent lighting circuits were not listed and marked "SWD." a) 1204 E. 12th St., Wilmington, DE 19802 (Building #3 Panel #3): On or about August 3, 2023, and at times prior thereto and thereafter, employees were exposed to potential arc flash and electrical shock while using non "SWD" circuit breaker to activate and deactivate overhead fluorescent lights that operated in 120V and 277 Volt systems. b) 1204 E. 12th St., Wilmington, DE 19802 (Building #3 Panel #4): On or about August 3, 2023, and at times prior thereto and thereafter, employees were exposed to potential arc flash and electrical shock while using NON "SWD" circuit breaker to activate and deactivate overhead fluorescent lights that operated in 120V and 277 Volt systems.