Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1148175.015
Citation: 01009B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 07/27/2016
Nr Instances: 3
Nr Exposed: 4
Abatement Date: 09/13/2016
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 08/16/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/16/2016 | $0.00 | 09/13/2016 | Serious | |
Penalty | Z: Issued | 07/27/2016 | $0.00 | 09/13/2016 | Serious |
Text For Citation: 01 Item/Group: 009B Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Power House: On, or about, May 25, 2016, live parts of the electrical system were enclosed or other effective means to prevent contact had not been provided: A. Panelboard LC3 - the live buss feeding the panel and connections on either side of the overcurrent devices were exposed. B. Main Switch: The buss bars located behind the switch were exposed. C. Main Control Panel: The buss bars located behind the panel were exposed.