Violation Detail
Standard Cited: 19100119 J05 Process safety management of highly hazardous chemicals.
Inspection Nr: 1013183.015
Citation: 01009B
Citation Type: Other
Abatement Date: 06/10/2015 2
Initial Penalty: $0.00
Current Penalty: $2,600.00
Issuance Date: 05/04/2015
Nr Instances: 1
Nr Exposed: 19
Related Event Code (REC):
Gravity:
Report ID: 0521100
Contest Date: 05/28/2015
Final Order: 06/08/2016
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/08/2016 | $2,600.00 | 06/10/2015 | Other | |
Penalty | C: Contested | 06/11/2015 | $0.00 | 06/10/2015 | Serious | |
Penalty | Z: Issued | 05/04/2015 | $0.00 | 06/10/2015 | Serious |
Text For Citation: 01 Item/Group: 009B Hazard:
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) before use: a) On or about December 19, 2014, a Building #5 Ammonia Refrigeration Engine Room man door and sliding door were not tight fitting as required by American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) 15-2010 Safety Standard for Refrigeration Systems, Section 8.12(b) and/or International Institute of Ammonia Refrigeration (IIAR) 2-2008 Equipment, Design, and Installation of Closed-Circuit Ammonia Mechanical Refrigeration Systems, Section 13.3.3.1.