Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1812503.015
Citation: 01009A
Citation Type: Serious
Abatement Status: Quick Fix
Initial Penalty: $5,627.00
Current Penalty: $3,938.90
Issuance Date: 08/01/2025
Nr Instances: 2
Nr Exposed: 4
Abatement Date:
Gravity: 5
Report ID: 0523900
Contest Date:
Final Order: 09/10/2025
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/10/2025 | $3,938.90 | Serious | ||
Penalty | Z: Issued | 08/01/2025 | $5,627.00 | Serious |
Text For Citation: 01 Item/Group: 009A Hazard:
29 CFR 1910.303(g)(2)(i): Live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by approved cabinets or other forms of approved enclosures, or other means listed under this provision: (a) Sawing area, chop saw infeed conveyor motor; On or about March 18, 2025, and dates prior, wire-nut connector splices on energized conductor wires that provide 240 volt AC power to the chop saw infeed conveyor motor were not protected by an enclosure, elevation, or other acceptable means. (b) Sawing area, chop saw; On or about March 18, 2025, and dates prior, energized conductors and contactor switches carrying 240 volt AC to the chop saw were not protected by an enclosure, elevation, or other acceptable means.