Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1550498.015
Citation: 01009A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,315.00
Current Penalty: $3,315.00
Issuance Date: 02/09/2022
Nr Instances: 2
Nr Exposed: 1
Abatement Date: 03/03/2022
Gravity: 5
Report ID: 0523300
Contest Date: 03/08/2022
Final Order: 07/05/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 07/05/2022 | $3,315.00 | 03/03/2022 | Serious | |
Penalty | C: Contested | 03/09/2022 | $3,315.00 | 03/03/2022 | Serious | |
Penalty | Z: Issued | 02/09/2022 | $3,315.00 | 03/03/2022 | Serious |
Text For Citation: 01 Item/Group: 009A Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: a) On or about August 30, 2021, the conductors supplying electrical power to the Newman planer (Model S-282) in Plant 1 were not protected from abrasion due to the flexible conduit being pulled away from the motor junction box. b) On or about August 30, 2021, the conductors for the lumber conveyor in Plant 1 were not protected from physical damage due to the floor mounted conduit being pulled away from the floor-mounted cutout box.