Violation Detail
Standard Cited: 19100119 F01 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 1361878.015
Citation: 01009A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,934.00
Current Penalty: $13,260.00
Issuance Date: 05/24/2019
Nr Instances: 1
Nr Exposed: 42
Abatement Date: 10/31/2019
Gravity: 10
Report ID: 0317300
Contest Date: 06/14/2019
Final Order: 11/20/2019
Related Event Code (REC): R
Emphasis:
Substance: 1190
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/20/2019 | $13,260.00 | 10/31/2019 | Serious | |
Penalty | C: Contested | 06/17/2019 | $11,934.00 | 06/20/2019 | Serious | |
Penalty | Z: Issued | 05/24/2019 | $11,934.00 | 06/20/2019 | Serious |
Text For Citation: 01 Item/Group: 009A Hazard:
29 CFR 1910.119(f)(1)(i)(D): The employer did not develop and implement written operating procedures that provide clear instructions for safely conducting activities involved in each covered process consistent with the process safety information that addressed emergency shutdown including the conditions under which emergency shutdown is required, and the assignment of shutdown responsibility to qualified operators to ensure that emergency shutdown is executed in a safe and timely manner: a) Ethylene Oxide Continuous Plant, Croda-Atlas Point. - On or about November 25, 2018, the employer failed to develop and implement written operating procedures to de-inventory the ethylene oxide from equipment, such as (but not limited to) that contained in the Purification Tower (T-430), to divert ethylene oxide away from Purification Column Steam Reboiler E-430, the location of the compromised flange leaking ethylene oxide, contributing to employee exposure to ethylene oxide.