Violation Detail
Standard Cited: 19100335 A01 I Safeguards for personnel protection.
Inspection Nr: 1828555.015
Citation: 01009
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,094.00
Current Penalty: $4,965.80
Issuance Date: 09/17/2025
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 11/04/2025
Gravity: 5
Report ID: 0112000
Contest Date: 10/06/2025
Final Order: 02/05/2026
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 02/05/2026 | $4,965.80 | 11/04/2025 | Serious | |
| Penalty | C: Contested | 10/06/2025 | $7,094.00 | 11/04/2025 | Serious | |
| Penalty | Z: Issued | 09/17/2025 | $7,094.00 | 11/04/2025 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.335(a)(1)(i):Employees working in areas where there were potential electrical hazards were not provided with and required to wear electrical protective equipment that was appropriate for the specific parts of the body that needed to be protected and for the work being performed: On, or about, July 1, 2025, in the following locations, personal protective equipment such as, but not limited to, voltage rated gloves, fire resistive clothing, face shields, balaclavas, hard hats and hearing protection were not provided to employees who performed live electrical work, including trouble-shooting, or who verified that electrical equipment was properly de-energized: A. Engineering Area: Employees used multi-meters to check for proper wiring in control boxes of equipment that was being designed, and built. B. Maintenance: Employees used multi-meters and other test equipment to perform diagnostic testing and to confirm absence of voltage before working on equipment.
Translate