Violation Detail
Standard Cited: 19100334 A02 I Use of equipment.
Inspection Nr: 1655159.015
Citation: 01009
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $10,046.00
Current Penalty: $5,023.00
Issuance Date: 06/13/2023
Nr Instances: 2
Nr Exposed: 7
Abatement Date: 08/01/2023
Gravity: 5
Report ID: 0420600
Contest Date:
Final Order: 07/12/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/12/2023 | $5,023.00 | 08/01/2023 | Serious | |
Penalty | Z: Issued | 06/13/2023 | $10,046.00 | 08/01/2023 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.334(a)(2)(i): Portable cord and plug connected equipment and flexible cord sets (extension cords) were not visually inspected before use on any shift for external defects (such as loose parts, deformed and missing pins, or damage to outer jacket or insulation) and for evidence of possible internal damage (such as pinched or crushed outer jacket): a: At 911 - B Rivo Place Tarpon Springs, Florida; On or about March 8, 2023, at the polishing department, power and flexible cords used to energize equipment and hand tools such as grinders and light fixtures. In that, cords were observed with damaged outer sheath covers, splices, damaged covered with electrical tape, separated from the strain relief, knotted, unmounted hanging from the ceiling, installed through wall holes, and daisy chained. b: At 911 - B Rivo Place Tarpon Springs, Florida; On or about March 8, 2023, at the welding department, power and flexible cords used to energize equipment and hand tools such as grinders, light fixtures, welding systems. In that, cords were observed with damaged outer sheath covers, splices, deformed, damaged covered with electrical tape, separated from the strain relief, knotted, missing knockouts, unmounted on the floor, installed through wall holes, and daisy chained.