Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1523431.015
Citation: 01009
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,851.00
Current Penalty: $2,925.50
Issuance Date: 09/24/2021
Nr Instances: 2
Nr Exposed: 315
Abatement Date: 10/21/2021
Gravity: 1
Report ID: 0214500
Contest Date:
Final Order: 12/17/2021
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/17/2021 | $2,925.50 | 10/21/2021 | Serious | |
Penalty | Z: Issued | 09/24/2021 | $5,851.00 | 10/21/2021 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.303(f)(2):Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident. a) Warehouse different locations: The panel box was not legibly marked to indicate its purpose of the circuit breakers, on or about 7/22/21. b) Warehouse different locations: The panel box was not legibly marked to indicate its purpose of the circuit breakers, on or about 8/4/21.