Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1508036.015
Citation: 01009
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,022.00
Current Penalty: $4,213.20
Issuance Date: 01/25/2021
Nr Instances: 3
Nr Exposed: 3
Abatement Date: 03/18/2021
Gravity: 5
Report ID: 0729700
Contest Date:
Final Order: 02/18/2021
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/18/2021 | $4,213.20 | 03/18/2021 | Serious | |
Penalty | Z: Issued | 01/25/2021 | $7,022.00 | 02/19/2021 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: Employees engaged in grain handling activities were exposed to fire and electrical shock hazards in that the disconnecting means, circuit breaker boxes at the following locations were not properly labeled to indicate their intended use for the equipment listed below. a) Chemical Shed by the front entrance door - Four (4) of the Disconnect D Safety Switch boxes not label. b) Inside the Chemical Shed by the Control Room for the Dried Fertilizer area - Two (2) of the D Safety Switch boxes not labeled. c) Inside the Chemical Shed by the Control Room for the Dried Fertilizer area - One (1) Circuit Breaker box not label for all the fuse slots. 29 CFR 1903.19(c)(1) requires certification that the abatement of the above violation is complete.