Violation Detail
Standard Cited: 19100119 J05 Process safety management of highly hazardous chemicals.
Inspection Nr: 1411622.015
Citation: 01009
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $13,260.00
Current Penalty: $13,260.00
Issuance Date: 12/19/2019
Nr Instances: 2
Nr Exposed: 3
Abatement Date: 02/07/2020
Gravity: 10
Report ID: 0317000
Contest Date: 01/06/2020
Final Order: 01/04/2021
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | F: Formal Settlement | 01/04/2021 | $13,260.00 | 02/07/2020 | Serious | |
| Penalty | C: Contested | 01/14/2020 | $13,260.00 | 02/07/2020 | Serious | |
| Penalty | Z: Issued | 12/19/2019 | $13,260.00 | 02/07/2020 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that were outside acceptable limits (defined by the process safety information on paragraph (d) of this section) in a safe and timely manner when necessary means where taken to assure safe operation. a) Philadelphia Energy Solutions Refinery Complex, 3144 Passyunk Ave, Philadelphia, PA 19145 - HF Alkylation Unit 433: On or about June 21, 2019, the employer did not correct deficiencies in HF spray mitigation pumps (P-1150A & B) in a timely manner to assure pumps met the hydraulic curve at 150 percent during an emergency. Employees working on and in the vicinity of equipment containing highly hazardous chemicals are exposed to fire, explosion, toxics, and corrosive hazards. b) Philadelphia Energy Solutions Refinery Complex, 3144 Passyunk Ave, Philadelphia, PA 19145 - HF Alkylation Unit 433: On or about June 20, 2019, the employer did not correct deficiency in HF spray mitigation pump (P-1150B) when employees had to manually start P-1150B during the event due to a remote pump start failure. Employees working on and in the vicinity of equipment containing highly hazardous chemicals are exposed to fire, explosion, toxics, and corrosive hazards.
Translate