Violation Detail
Standard Cited: 19100305 B03 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1357172.015
Citation: 01009
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $4,240.00
Current Penalty: $1,000.00
Issuance Date: 11/29/2018
Nr Instances: 3
Nr Exposed: 9
Abatement Date:
Gravity: 1
Report ID: 0636900
Contest Date:
Final Order: 12/13/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/13/2018 | $1,000.00 | Serious | ||
Penalty | Z: Issued | 11/29/2018 | $4,240.00 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.305(b)(3)(ii): 29 CFR 1910.305(b)(3)(ii): Boxes shall be closed by suitable covers securely fastened in place, boxes were not closed as required. In the shop areas, the employer did not ensure the electrical panel boxes located in the production areas to energize machinery were effectively closed during operations and were left open: a) In the press brake area, panel box on the east side. b) In the north well section, panel boxes on the north side. c) In the brake department, panel door open with live wires.