Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1269702.015
Citation: 01009
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,114.00
Current Penalty: $4,979.00
Issuance Date: 01/19/2018
Nr Instances: 2
Nr Exposed: 6
Abatement Date: 01/29/2018
Gravity: 5
Report ID: 0111100
Contest Date:
Final Order: 02/12/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 02/12/2018 | $4,979.00 | 01/29/2018 | Serious | |
Penalty | Z: Issued | 01/19/2018 | $7,114.00 | 01/29/2018 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Working space in front of electrical breaker panels was less than three feet, in the following instances: a) Southeast Side of Maintenance Workshop - Access to the two breaker panels was blocked by the red toolbox/work bench. b) Northwest Side of Maintenance Workshop - Access to the single breaker panel was blocked by fuel cans, cardboard box and other debris.