Violation Detail
Standard Cited: 19100304 B04 II B Wiring design and protection.
Inspection Nr: 1016847.015
Citation: 01009
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,000.00
Current Penalty: $4,000.00
Issuance Date: 02/12/2015
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 04/15/2015
Gravity: 5
Report ID: 0936200
Contest Date:
Final Order: 03/02/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/02/2015 | $4,000.00 | 04/15/2015 | Serious | |
Penalty | Z: Issued | 02/12/2015 | $4,000.00 | 03/11/2015 | Serious |
Text For Citation: 01 Item/Group: 009 Hazard:
29 CFR 1910.304(b)(4)(ii)(B): Where connected to a branch circuit supplying two or more receptacles or outlets, a receptacle may not supply a total cord- and plug-connected load in excess of the maximum specified in Table S-4: Bldg. 660, Bay 1, Raw Stock Area: A 20 amp branch circuit supplying two or more receptacle outlets was supplying a load of 31.5 amps where table S-4 indicates the maximum load is 16 amps.