Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1340849.015
Citation: 01008G
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/19/2018
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 12/07/2018
Gravity: 10
Report ID: 0522000
Contest Date:
Final Order: 11/08/2018
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/08/2018 | $0.00 | 12/07/2018 | Serious | |
Penalty | Z: Issued | 10/19/2018 | $0.00 | 12/07/2018 | Serious |
Text For Citation: 01 Item/Group: 008G Hazard:
29 CFR 1910.307(c): Electrical installations. Equipment, wiring methods, and installations of equipment in hazardous (classified) locations shall be intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. Requirements for each of these options are as follows: a) On or about 8/22/2018 an employer did not ensure that the electrical equipment, electrical wiring and installation was intrinsically safe, wiring and electrical components must be approved for Class II Division I electrical installations, due to the amount of combustible dust located in areas such as but not limited to the area of the Biesse routers and the area behind the Cantek belt sander.