Violation Detail
Standard Cited: 19100305 B02 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1340849.015
Citation: 01008F
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/19/2018
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 12/07/2018
Gravity: 10
Report ID: 0522000
Contest Date:
Final Order: 11/08/2018
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/08/2018 | $0.00 | 12/07/2018 | Serious | |
Penalty | Z: Issued | 10/19/2018 | $0.00 | 12/07/2018 | Serious |
Text For Citation: 01 Item/Group: 008F Hazard:
29 CFR 1910.305(b)(2)(i): All pull boxes, junction boxes, and fittings shall be provided with covers identified for the purpose. If metal covers are used, they shall be grounded. In completed installations, each outlet box shall have a cover, faceplate, or fixture canopy. Covers of outlet boxes having holes through which flexible cord pendants pass shall be provided with bushings designed for the purpose or shall have smooth, well-rounded surfaces on which the cords may bear. a)On or about 8/22/2018 the employer did not provide covers for the circuit breaker boxes and junction boxes in locations such as but not limited to the planers on the first floor, exposing employees to an electrocution hazard.