Violation Detail
Standard Cited: 6A0001 General Duty Clause
Inspection Nr: 311211296
Citation: 01008E
Citation Type: Serious
Abatement Status: E
Initial Penalty:
Current Penalty:
Issuance Date: 05/03/2010
Nr Instances: 1
Nr Exposed: 30
Abatement Date: 06/18/2010
Gravity: 10
Report ID: 0257260
Contest Date: 05/21/2010
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | J: ALJ Decision | 04/26/2012 | 06/18/2010 | Serious | ||
| Penalty | Z: Issued | 05/03/2010 | 06/18/2010 | Serious |
Text For Citation: 01 Item/Group: 008E Hazard: EXPLOSION
Section 6(a) of the Puerto Rico Occupational Safety and Health Act: The employer did not furnish employment and a place of employment which were free from recognized hazards that were causing or likely to cause death or physical harm to employees in that employees were exposed to: Seccion 6(a) de la Ley de Seguridad y Salud en el Trabajo de Puerto Rico: El patrono no proveyo empleo y un sitio de empleo libre de riesgos reconocidos que esten causando o que puedan causar muerte o dano fisico a los empleados, por cuanto empleados estaban expuestos a: API - 2610 - MAYO 2005 is a recognized Industry standard of recommended practices that covers Design, Construction, Operation, Maintenance, and Inspection of Terminal & Tank Facilities associated with marketing, refining, pipeline, and other similar activities. The purpose of this standard is to consolidate a wide base of current industry experience, knowledge, information, and management practices into a cohesive standard compromising a range of best practices. a)At Caribbean Petroleum Refining in Bayamon employees that worked performing routine tasks such as tank operator, waste treatment operator, loading rack operator, among others were exposed or could be exposed to flammable and combustible spills or release, fire and or explosion during the performance of there duties. In the Tank Farm Area there was approximately 45 above ground steel tanks ranging in capacity from 500 to 500,000 barrels which were used for the storage and distribution of gasoline, diesel, fuel oil, and jet fuel. Products were transfer to and from the tanks via above and under ground pipelinesThe employer does not have an inspection system for the entire system of pipes in service, to determine the intregrity of product transfer piping at the facility. The employer provided some documentation of daily and monthly inspection for visible leak to the Pipes racks. This inspection was to comply with SPCC and does not comply with the API 570 - 5.5.4 External Visual Inspection. In 2007, the employer inspected aboveground pipeline from dock to plant but did not inspected the the entire pipeline system inside the facility. Among other methods, one feasible and acceptable abatement method to correct this hazard is: 1.Follow API 2610 - 10.6.1 Pipeline Integrity Assurance of Existing Piping System; General. All facilities shall periodically assure the integrity of system piping. The integrity of buried piping systems shall be assured by a comprehensive program utilizing a combination of the methods in 10.6.3. The integrity of aboveground piping systems shall be assessed by one of the methods in 10.6.2. API - 2610 - MAYO 2005 es un reglamento de practicas reconocidas por la industriaque abarca el Diseno, Construccion, Operacion, Mantenimiento e Inspecciones de Facilidades de Terminal y Tanques asociadas con mercadeo, refinacion, sistema de tuberia y otras actividades similares. El proposito de este reglamento es consolidar con una base considerable de experiencia en la industria actualizado, conocimiento, informacion y practicas gerenciales en un reglamento consistente comprometiendo una gama de las mejores practicas. a)En Caribbean Petroleum Refining en Bayamon empleados que trabajaban realizando tareas tales como operador de tanque operador de tratamiento de aguas, operador de carga entre otras fueron expuestos o podrian estar expuesto a derrame, liberacion de productos quimicos inflamables, combustible,fuego y/o explosion durante el desempeno de sus deberes. En la granja de tanques habian alrededor de 45 tanques de acero sobre el terreno, con capacidades que fluctuaban entre 500 a 500,000 barriles los cuales se utilizaban en el almacenamiento y distribucion de gasolina, diesel, aceite combustible y combustible para aviones. Los productos fueron transferidos desde y hacia los tanques, a traves de tuberias que estaban por encima y por debajo del terreno El patrono no tenia un sistema de inspeccion para el sistema completo de tuberias en servicio para determinar la integridad de transferencia de producto en la facilidad. El patrono proveyo documentacion escrita de algunas inspecciones diarias y mensuales para fugas visibles en los racks de tuberias. Esta inspeccion era para cumplir con SPCC y no cumplia con el API 570 - 5.5.4 Inspeccion Visual Externa. El 2007, el patrono examino la tuberia sobre el terreno desde el puerto hasta la planta pero no examino el sistema completo de tuberias dentro de la facilidad. Un metodo seguro entre otros metodos aceptables para corregir estos riesgos son: 1.Seguir el API 2610 - 10.6.1 Certeza de Integridad de las Tuberias del Sistema de Tuberias Existentes; General. Todas las facilidades deben periodicamente asegurar la integridad del sistema de tuberias. La integridad de sistemas de tuberia soterrada deben ser aseguradas por un programa extenso utilizando una combinacion de los metodos en el 10.6.3. La integridad de los sistemas de tuberias sobre el terreno deben ser aseguradas por uno de los metodos en el 10.6.2.
Translate