Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1340849.015
Citation: 01008E
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 10/19/2018
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 12/07/2018
Gravity: 10
Report ID: 0522000
Contest Date:
Final Order: 11/08/2018
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 11/08/2018 | $0.00 | 12/07/2018 | Serious | |
Penalty | Z: Issued | 10/19/2018 | $0.00 | 12/07/2018 | Serious |
Text For Citation: 01 Item/Group: 008E Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in cabinets, boxes, and fittings shall be effectively closed. a) On or about 8/22/2018 employees were exposed to electrical hazards due to openings in live electrical components located throughout the facility in such areas but not limited to a circuit breaker cabinet and the 480 electric control panel located on the wall behind the blue conveyer belt located in building #3 has unused openings, exposing employees to live electrical components.