Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1372854.015
Citation: 01008B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,630.00
Current Penalty: $0.00
Issuance Date: 04/10/2019
Nr Instances: 2
Nr Exposed: 5
Abatement Date: 05/31/2019
Gravity: 5
Report ID: 0626300
Contest Date:
Final Order: 05/06/2019
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/06/2019 | $0.00 | 05/31/2019 | Serious | |
| Penalty | Z: Issued | 04/10/2019 | $6,630.00 | 04/22/2019 | Serious |
Text For Citation: 01 Item/Group: 008B Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a) The employer did not close unused openings on electrical equipment. This violation occurred on or about January 16, 2019, and at times after thereto: a. In the Press department, electrical panel "press room S2" had openings of 1/4-inch at circuit breakers #7, #8, #13, and #14. b. In the Finishing department, two (2) circuit breakers were missing from the Spectra Series power panel board.