Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1269114.015
Citation: 01008B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 04/06/2018
Nr Instances: 2
Nr Exposed: 7
Abatement Date: 11/30/2018
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 04/30/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 11/07/2018 | $0.00 | 11/30/2018 | Serious | |
Penalty | P: Petition to Mod Abatement | 09/13/2018 | $0.00 | 10/30/2018 | Serious | |
Penalty | P: Petition to Mod Abatement | 06/28/2018 | $0.00 | 08/30/2018 | Serious | |
Penalty | I: Informal Settlement | 04/30/2018 | $0.00 | 06/29/2018 | Serious | |
Penalty | Z: Issued | 04/06/2018 | $0.00 | 05/02/2018 | Serious |
Text For Citation: 01 Item/Group: 008B Hazard:
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment a) GEA/FES ammonia refrigeration system: The employer did not perform inspections and tests on the safety interlocks for the hot gas defrost cycle on Spiral Air Unit Coolers LK 18 and LK 19, on or about 10/10/2017. b) Frick ammonia refrigeration system: The employer did not perform inspections and tests for the safety interlocks for the hot gas defrost cycle on Spiral Freezer Coils SP1 C1-C4, on or about 10/10/2017. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM, FAILURE TO DO SO WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 AS PER 29 CFR 1903.19.