Violation Detail
Standard Cited: 19100305 E01 Wiring methods, components, and equipment for general use.
Inspection Nr: 1133442.015
Citation: 01008B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/16/2016
Nr Instances: 1
Nr Exposed: 3
Abatement Date: 09/26/2016
Gravity: 10
Report ID: 0419400
Contest Date: 10/07/2016
Final Order: 04/21/2017
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 04/21/2017 | $0.00 | 09/26/2016 | Serious | |
Penalty | C: Contested | 10/25/2016 | $0.00 | 09/26/2016 | Serious | |
Penalty | Z: Issued | 09/16/2016 | $0.00 | 09/26/2016 | Serious |
Text For Citation: 01 Item/Group: 008B Hazard:
29 CFR 1910.305(e)(1): Cabinets, cutout boxes, fittings, boxes, and panelboard enclosures in damp or wet locations were not installed to prevent moisture or water from entering and accumulating within the enclosures: (a) Chemical Room - On or about June 8, 2016, employees were exposed to the hazard or contacting an energized source due to an electrical outlet being installed directly beneath the chemical central dispensing system. Corrosive chemical had leaked on and corroded the outlet and conduit.