Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1355282.015
Citation: 01008A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,819.00
Current Penalty: $3,000.00
Issuance Date: 03/27/2019
Nr Instances: 4
Nr Exposed: 18
Abatement Date: 04/24/2019
Gravity: 5
Report ID: 0636900
Contest Date:
Final Order: 04/22/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/22/2019 | $3,000.00 | 04/24/2019 | Serious | |
Penalty | Z: Issued | 03/27/2019 | $6,819.00 | 04/24/2019 | Serious |
Text For Citation: 01 Item/Group: 008A Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions. On or about October 22, 2018, and at times prior there to, in the old break room building, electrical outlet boxes used to energize portable equipment wiring was not protected from abrasions when ran into metal knock-outs, exposing employees to electrical shock hazards: a) On the north wall, two (2) electrical outlets without wire protection; and b) On the south wall, two (2) electrical outlets without wiring protection.