Violation Detail
Standard Cited: 19100252 C01 III General requirements.
Inspection Nr: 1162230.015
Citation: 01008A
Citation Type: Serious
Abatement Date: 02/03/2017 2
Initial Penalty: $8,730.00
Current Penalty: $5,238.00
Issuance Date: 01/13/2017
Nr Instances: 2
Nr Exposed: 3
Related Event Code (REC):
Gravity: 10
Report ID: 0215800
Contest Date: 02/07/2017
Final Order: 05/30/2017
Emphasis:
Substance: 0731
Substance: 1520
Substance: 1620
Substance: 2587
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 05/30/2017 | $5,238.00 | 02/03/2017 | Serious | |
Penalty | C: Contested | 02/23/2017 | $8,730.00 | 02/03/2017 | Serious | |
Penalty | Z: Issued | 01/13/2017 | $8,730.00 | 02/03/2017 | Serious |
Text For Citation: 01 Item/Group: 008A Hazard:
29 CFR 1910.252(c)(1)(iii): Local exhaust or general ventilating systems were not provided and arranged to keep the amount of toxic fumes, gases, or dusts below the maximum allowable concentration as specified in 29 CFR 1910.1000: a) Welding area, on or about 8/3/16: An employee performing air arc-ing was exposed to 44 milligrams per cubic meter (mg/m3) of total dust or 2.9 times the permissible exposure limit (PEL) of 15 mg/m3 during the 480 minute sampling period. Ventilation used was arranged in such a manner so as to draw air contaminants into the employees breathing zone. b) Welding area, on or about 8/3/16: An employee performing air arc-ing was exposed to 32 milligrams per cubic meter (mg/m3) of iron oxide fume or 3.2 times the permissible exposure limit (PEL) of 10 mg/m3 during the 480 minute sampling period. Ventilation used was arranged in such a manner so as to draw air contaminants into the employees breathing zone. c)) Welding area, on or about 8/3/16: An employee performing air arc-ing was exposed to 0.3 milligrams per cubic meter (mg/m3) of copper fume or 3.0 times the permissible exposure limit (PEL) of 0.1 mg/m3 during the 480 minute sampling period. Ventilation used was arranged in such a manner so as to draw air contaminants into the employees breathing zone. d) Welding area, on or about 8/3/16: An employee performing air arc-ing was exposed to 5.6 milligrams per cubic meter (mg/m3) of manganese fume or 1.1 times the Ceiling limit of 5.0 mg/m3 during the 480 minute sampling period. Ventilation used was arranged in such a manner so as to draw air contaminants into the employees breathing zone. Abatement documentation must be submitted for this item