Violation Detail
Standard Cited: 19100304 F01 IV Wiring design and protection.
Inspection Nr: 984505.015
Citation: 01008
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $3,080.00
Current Penalty: $1,000.00
Issuance Date: 01/06/2015
Nr Instances: 3
Nr Exposed: 8
Abatement Date: 02/24/2015
Gravity: 5
Report ID: 0112000
Contest Date: 07/06/2020
Final Order: 07/06/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | C: Contested | 07/30/2020 | $3,080.00 | 02/24/2015 | Serious | |
Penalty | F: Formal Settlement | 07/06/2020 | $1,000.00 | 02/24/2015 | Serious | |
Penalty | Z: Issued | 01/06/2015 | $3,080.00 | 02/24/2015 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.304(f)(1)(iv): Overcurrent devices for circuits rated 600 volts, nominal, or less, were not readily accessible to each employee or authorized building management personnel: PRODUCTION AREA: On or about July 10, 2014, the employer did not ensure that the working space about electrical panels was clear of stored items for a minimum of three feet and that the panels were accessible. A) Panels LPL and LPN were blocked by the battery chargers for Powered Industrial Vehicles (PIVs) as well as the PIVs themselves. B) Panel RP10 was blocked by chutes manufactured at the facility as well as shovels, a dust mop, a box and other debris. C) Panel LPJ was blocked by a shovel and chutes manufactured at the facility.