Violation Detail
Standard Cited: 19100119 L01 Process safety management of highly hazardous chemicals.
Inspection Nr: 313796732
Citation: 01008
Citation Type: Serious
Abatement Status: X
Initial Penalty: $7,000.00
Current Penalty: $5,000.00
Issuance Date: 07/07/2010
Nr Instances: 2
Nr Exposed: 226
Abatement Date: 12/31/2010
Gravity: 10
Report ID: 0111400
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 07/30/2010 | $5,000.00 | 12/31/2010 | Serious | |
| Penalty | Z: Issued | 07/07/2010 | $7,000.00 | 10/04/2010 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard: CHEMNEP
29 CFR 1910.119(l)(1): The employer did not establish and implement written procedures to manage changes to process chemicals, technology, equipment, and procedures; and changes to facilities that affect a covered process: The employer failed to establish and implement written procedures to manage changes in the ammonia refrigeration system such as: 1.Installation of Spiral Freezer #4/LVS Spiral Freezer on November 9, 2007 and associated piping; 2.Addition of an oil pot to Spiral Freezer #4 around March 2008; 3.Replacement of three condensers of different make and model from 2004 - 2008.