Violation Detail
Standard Cited: 19100304 F01 I Wiring design and protection.
Inspection Nr: 1598521.015
Citation: 01008
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $4,144.00
Current Penalty: $2,100.00
Issuance Date: 11/08/2022
Nr Instances: 5
Nr Exposed: 15
Abatement Date: 12/28/2022
Gravity: 5
Report ID: 0111700
Contest Date:
Final Order: 12/16/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/16/2022 | $2,100.00 | 12/28/2022 | Serious | |
Penalty | Z: Issued | 11/08/2022 | $4,144.00 | 12/28/2022 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.304(f)(1)(i):Conductors and equipment were not protected from overcurrent in accordance with their ability to safely conduct current: Site- Employees were not protected from electric shock and burns where branch circuit conductors were not compatible with the overcurrent protection from the circuit breaker which they were wired. Circuit breakers rated for 30, 40, and 60 amps; providing overcurrent protection to 220-volt outlet receptacles in all three panel boards located in the repair department; were installed using #12 wire and only rated for 20 amps.