Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1577743.015
Citation: 01008
Citation Type: Serious
Abatement Date: 04/08/2022 2
Initial Penalty: $8,287.00
Current Penalty: $5,500.00
Issuance Date: 03/11/2022
Nr Instances: 1
Nr Exposed: 200
Related Event Code (REC):
Gravity: 5
Report ID: 0213600
Contest Date:
Final Order: 04/11/2022
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/11/2022 | $5,500.00 | 04/08/2022 | Serious | |
Penalty | Z: Issued | 03/11/2022 | $8,287.00 | 04/25/2022 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled equipment was not installed and used in accordance with any instructions included in the listing and labeling. a) On or about 02/08/2022, Throughout establishment, receptacle boxes that are designed to be mounted to a wall as per the National Electrical Code were incorrectly being used as pendant drop outlets to supply power to manufacturing areas exposing employees to electrical shock. ABATEMENT CERTIFICATION REQUIRED